E1854EL
|
Type |
Overall dimensions, mm, max |
Weight, kg, max. |
|
E1854EL |
24 х 111 х 116 |
0.3 |
|
Input signal |
0...0.5 A, 0...1 A, 0...2.5 A, 0...5 A, 0...125 V, 0...250 V, 0...500 V, 75...125 V, 150...250 V |
|
Basic error limits |
±0,5% |
|
Temperature range (operating) |
-40 °С... +50 °С |
|
Protection extent |
IP50 |
|
Installation |
DIN-rail of 35 mm |
|
Interface |
RS485 (Мodbus RTU) – main, for data transmission |
|
Data rate |
4800, 9600, 19200, 38400 bit/s. |
|
Parameters setting (reprogramming) through the interface |
– digital output – interface RS485 (Modbus RTU) parameters – analogue output signal parameters |
|
Analogue output (Accuracy class 0,5) |
Quantity: 0, 1 Ranges: 0...5 mA; 0…20 mA; 4...20 mA |
|
Digital output |
DC voltage: 300 V; 100 mA AC voltage: 200 V; 100 mA |
|
Maximum input signal overload |
150%, duration of 2 hours |
|
Time of setting output analogue signal, max |
0.5 s |
|
Power supply |
– 220 VU, 85...253 VAC, – 50 Hz or 120...265 VDC – 230 V, 85...253 VAC, 50 Hz – 12 VN (12+6/-3) VDC – 24 VN (24+12/-6) VDC |
|
Power consumption from power circuit, max. |
6.0 V•А |
|
Calibration interval |
8 years |
|
Guarantee period |
2 years |
|
Mean life |
20 years |
|
Mean time between failures |
200000 hours |
E1854EL – а – b – с – d – f
a – input signal measurement ranges:
0...0.5 A, 0...1 A, 0...2.5 A, 0...5 A,
0...125 V, 0...250 V, 0...500 V, 75...125 V,
150...250 V
b – supply voltage:
220VU – universal power:
supply voltage of 85...253 VAC, 50 Hz or 120 ...265 VDC;
230 V – supply voltage of 85...253 VAC, 50 Hz;
12 VN – (12+6/-3) VDC;
24 VN – (24+12/-6) VDC
c – measurement range analogue output signal:
А = 0...5 mA; В = 4...20 mA; С = 0...20 mA;
х with the absence
d – digital output availability:
х – no output
01 – one digital output
f – custom design:
А – operation at NPP
(safety class – 4)
With the absence of custom design.
Ordering example
E1854EL – 0…2.5 A – 12 VN – В – 01 – А TU 25-7504.226-2014
For the transducer with the following characteristics: E1854EL transducer type, measurement range input signal of 0... 2.5 A, supply voltage of (12+6/-3) VDC, measurement range output signal of 4…20 mA, digital output, for operation at NPP (safety class 4).