SchP02P, SchP72P, SchP96P, SchP120P

Meters are intended to measure and convert the effective value of current, voltage and frequency in one-phase and three-phase AC circuits into output unified DC signals and to transmit measured values through serial digital interface RS485, which allow using meters in automated systems of various purpose.
The meters have the possibility of programming with built-in buttons or through interface RS485:
– Indication range, position of decimal point;
– level of controlled input signals (settings);
– change in brightness of digital indicators illumination;
– interface parameters.
SchP120P meets the requirements of PJSC ROSSETI and PJSC FGC UES, they are recommended for the use at facilities of JSC ROSSETI and PJSC FGC UES.





Specifications
Documentation
Overall drawings
Related products

Type

Overall dimensions, mm

Panel cutout, mm

Sign height, mm

Weight, kg, max.

SchP02P

96 х 48 х 148

92х45

20

0.4

SchP72P

72 х 72 х 103

68х68

14

0.2

SchP96P

96 х 96 х 103

92х92

20

0.5

SchP120P

120 х 120 х 103

112х112

20

0.5

Accuracy class

when measuring:

when conversion:

0.2 or 0.5

0.5

Temperature range (operating)

UKhL3.1 (-40 °С... +70 °С)

Maximum indication range

0...9999

Frequency range measured/converted signals

45 ... 65 Hz (300...500 Hz)

Number of measuring channels

1

Number of displayed parameters

1 or 2 (SchP72P, SchP96P, SchP120P) for displaying input signal frequency

Galvanic isolation of input and output circuits, power circuits

Yes

Front frame protection level

IP50

Interface RS485 (protocol Modbus RTU)

– Basic for data transmission (for SchP120P, manufacture without RS485 is possible);

– Additional for data transmission or connection of the Display panel (MI120, MI80) and the display

Interface exchange rate

4600, 9600, 19200, 38400, 115200 bit/s.

(115200 bit/s is set through SW “Configuration Manager”)

Analogue output (accuracy class 0.5)

Quantity: 0; 1; 2;

Ranges: 0...5 mA, 4...20 mA, 0…20 mA, 0...2.5...5 mA, 4...12...20 mA, 0…10…20 mA

Load resistance

2.5 kΩ for ranges of 0...5 mA, 0...2.5...5 mA

0.5 kΩ for ranges of 0...20 mA, 4...20 mA,

4...12...20 mA, 0…10…20 mA

Digital output

Quantity: 0; 1; 2;

DC voltage 300 V, 100 mA or

AC voltage 200 V, 100 mA

Maximum permissible input signal overload (from the upper limit of the measurement range)

150% (1 minute)

Time of setting output analogue signal, max

1.0 s

Input resistance at voltage measurement, min.

(1-0.005) MΩ

Voltage drop when measuring current 500 mA, 1000 mA, 2000 mA, 1 A, 2 A, 5 A, max.

30 mV

Power supply

– 5 VN (5+4/-0.5) VDC,

– 12 VN (12+6/-3) VDC,

– 24 VN (24+12/-6) VDC,

– 220 VU (85...253 VAC, (50 ± 0.5) Hz or 120 ... 265 VDC),

– 220 V (85...253 VAC, (50 ± 0.5) Hz)

Power consumption, max.

2.5 V•A for SchP02P, SchP72P at supply voltage

5 VN, 12 VN, 24 VN

3.0 V•A for SchP96P, SchP120P at supply voltage

5 VN, 12 VN, 24 VN

6.0 V•A at supply voltage 220 VU, 230 V

Calibration interval

6 years

Guarantee period

36 months

Mean life

30 years

Mean time between failures

150000

Note: it is possible to connect the outer circuits according to the designation of connector contacts to the terminals “for screw” using a cord of up to 4 mm2 in cross-section, multi-core wires of up to 2.5 mm2. When connecting supply DC voltage of 120...265 V at supply voltage of 220 VU to power contacts “L”, “N”, any polarity is   possible.

Order form

SchPa – b1, b2 – с – d – e – f – g – h

а – meter type (by dimensions, mm):

SchP02P – 96×48,

SchP 72P – 72.72,

SchP 96P – 96.96,

SchP 120P – 120.120;

b1 – measurement range for the input signal of the main indicator with direct connection, transformation factor with connection through the outside current or voltage transformer:

mV: 100; 150; 200; 250; 500; 1000; 2000

V: 1; 2; 5; 10; 20; 50; 100; 150; 200; 250; 380; 500; 750

mA: 2; 5; 10; 20; 50; 100; 200; 500; 1000; 2000

А: 1; 2; 5

By default, frequency range input signal is 45...65 Hz (when ordering, it is not specified).

When ordering the meter with input signal frequency range 300…500 Hz only with the main indicator, specify reference designation 400 Hz in parameter b1 in brackets.

Note – If the indication range differs from the measurement range the input signal and from the transformation factor, give additionally the ordered indication range in the note to the order formula.

b2 – measurement range the input signal frequency of the additional indicator, except for meter ShP02P:

45...65 Hz – for range 45…65 Hz,

400 Hz – for range 300…500 Hz,

– with the absence, this parameter is not specified;

c – reference designation of supply voltage:

5 VN, 12 VN, 24 VN, 220 VU, 230 V;

d – availability of interfaces RS485:

1RS – one interface,

2RS – two interfaces;

х – with the absence of parameter (for SchP120P only);

e – reference designation of analogue and digital outputs:

02 – two digital outputs without analogue output,

11 – one analogue and one digital output,

12 – one analogue and two digital outputs,

20 – two analogue outputs without digital ones,

22 – two analogue and two digital outputs,

х – without analogue and digital outputs;

Note – the reference designation of analogue output is specified after figures in brackets: А – 0...5 mA, B – 4...20 mA, С – 0...20 mA, АР – 0…2.5…5 mA, ВР – 4…12…20 mA, СР – 0…10…20 mA, when ordering two analogue outputs, specify it separated by a comma.

f – indicators colour:

R – red,

G – green,

Y – yellow;

g – accuracy class: 0.2 or 0.5;

h – custom design:

ОМ2 - meters for marine application,

А – for operation at NPP (safety class 4), do not specify in other cases.

SchPa meter type

Full reference designation code parameter

b1, b2

с

d

e

f

g

h*

SchP02P

b1

+

1RS

х, 12, 20, 22

+

+

+

SchP72P

b1, b2

+

1RS

х, 02, 11, 20

+

+

+

SchP96P

b1, b2

+

1RS,2RS

х, 12, 20, 22

+

+

+

SchP120P

b1, b2

+

1RS,2RS

х, 12, 20, 22

+

+

+

b1

х

х

х

* For the meters with special design, accuracy class 0.5.

Notes

Sign “+” means that availability of all possible versions of a parameter in the order formula. Sign “x” means that no parameter is available.

Unused parameter h is not specified.

Ordering example

SchP120P – 500V, 45...65Hz – 220VU – 2RS – 22 (А,С) – К – 0.5 – ОМ2 TU 25-7504.219-2012

For SchP120P meter, main indicator – input signal measurement range 0...500 V, the additional indicator – frequency measurement range 45...65 Hz, supply voltage of 85...253 VAC, 50 Hz or 120...265 VDC, two interfaces RS485, two analogue outputs 0…5 mA and 0…20 mA, two digital output, red indicators, accuracy class 0.5, custom design ОМ2.