SchP00P, SchP01P, SchP02.01P
|
Type |
Overall dimensions, mm |
Sign height, mm |
Weight, kg, maximum |
|
SchP00P |
48 × 24 × 90 |
9.9 |
0.2 |
|
SchP01P |
96 × 24 × 90 |
9.9 |
0.2 |
|
SchP02.01P |
96 × 48 × 90 |
20 |
0.3 |
|
Accuracy class |
– when measuring AC intensity and voltage – 0.2 or 0.5; – when measuring input signal frequency – 0.05; – when converting – 0.5. |
|
Temperature range (operating) |
-40 °С…+50 °С |
|
Maximum indication range |
0... plus 9999 |
|
Frequency range measured/converted signals |
45 ... 65 Hz (by default), 300 ... 500 Hz (optionally, when ordering) |
|
Number of measuring channels |
1 |
|
Number of displayed parameters |
1 or 2 (the 2nd one for display of input signal frequency, sequential display) |
|
Galvanic isolation of input and output circuits, power circuits |
The meters have galvanic isolation in the power circuit, output circuits (SchP00P meters have no galvanic isolation in interface RS circuit) |
|
Protection extent on the front frame |
IP50 |
|
Interface RS485 (protocol Modbus RTU) |
Quantity: 0 or 1 |
|
Interface exchange rate |
9600, 19200, 38400, 57600 bit/s. |
|
Analogue output (accuracy class 0.5) |
Quantity: 0, 1, 2 Ranges: 0...5 mA, 4…20 mA, 0...20 mA, 0…2.5…5 mA, 4…12…20 mA, 0…10…20 mA |
|
Load resistance, kΩ |
0.5 (for 4...20 mA, 0...20 mA, 4…12…20 mA, 0…10…20 mA) 2.5 (for 0...5 mA, 0…2.5…5 mA) |
|
Digital output |
Quantity: 0; 1; 2; DC voltage 300 V, 100 mA or AC voltage 200 V, 100 mA |
|
Maximum permissible input signal overload |
150% |
|
Time of setting output analogue signal, max |
0.5 s |
|
Input resistance at voltage measurement, min. |
(1±0.005) MΩ |
|
Power supply |
– 5 V (5±0.25) VDC, – 12 V (12±0.6) VDC, – 24 V (24±1.2) VDC, – 5 VN (5+4/-0.5) VDC, – 12 VN (12+6/-3) VDC, – 24 VN (24+12/-6) VDC – outer unit of balanced power supply of 5 V (for SchP00P) |
|
Power consumption, max |
SchP00P – 1.7 VA; SchP01P – 2.7 VA; SchP02.01P – 3.2 VA |
|
Calibration interval |
10 years |
|
Guarantee period |
36 months |
|
Mean life, min |
20 years |
|
Mean time between failures |
200 000 h |
Order form
SchPa – b – с – d – e – f – g – h
SchPа – meter type (by the Overall dimension, mm):
SchP00P – 48×24,
SchP01P – 96×24,
SchP02.01P – 96×48,
b – reference designation of input signal measurement range:
mV: 100; 150; 200; 250; 500; 1000; 2000
V: 1; 2; 5; 10; 20; 50; 100; 150; 200; 250;
380 (except for SchP00P); 500 (except for SchP00P);
750 (except for SchP00P, SchP01P)
mA: 2; 5; 10; 20; 50; 100; 200; 500; 1000; 2000
А: 1; 2; 5
By default, frequency range input signal is 45...65 Hz (when ordering, it is not specified).
When ordering the meter with input signal frequency range 300…500 Hz, specify reference designation 400 Hz in parameter b in brackets.
Note: if the indication range differs from the measurement range the input signal and from the transformation factor, give additionally the ordered indication range in the note to the order formula.
c – reference designation of supply voltage:
5V, 12V, 24V, 5VN, 12VN, 24VN;
× – with outer unit of balanced power supply of 5 V (for SchP00P);
d – availability of interface RS485:
1RS – one interface,
× – no interface;
e – reference designation of analogue and digital outputs:
01 – one digital outputs without analogue outputs,
10 – one analogue output without digital input,
11 – one analogue and one digital output,
12 – one analogue and two digital outputs,
20 – two analogue outputs without digital ones,
22 – two analogue and two digital outputs,
× – no analogue and digital outputs
Note – reference designation of analogue output is specified after figures in brackets: А – 0...5 mA, В – 4...20 mA, С – 0...20 mA,
АР – 0…2.5…5 mA, ВР – 4…12…20 mA, СР – 0…10…20 mA, when ordering two analogue outputs, specify it separated by a comma;
f – indicators colour:
R – red, G – green, Y – yellow;
g – accuracy class:
0.2 or 0.5;
h – custom design:
А – for operation at NPP (safety class 4),
– with the absence of custom design parameter is not specified.
|
SchPa meter type |
Full reference designation code parameter |
||||||
|
b1 |
с |
d |
е |
f |
g |
h |
|
|
SchP00P |
b1 |
х, 5V, 12V, 24V |
х, 1RS |
X |
+ |
+ |
+ |
|
SchP01P |
b1 |
5V, 12V, 24V |
х, 1RS |
х,01,10,11 |
+ |
+ |
+ |
|
SchP02.01P |
b1 |
5VN, 12VN, 24VN |
1RS |
х, 12,20,22 |
+ |
+ |
+ |
|
Notes Sign “+” means that availability of all possible versions of a parameter in the order formula. Sign “x” means that no parameter is available in the order formula. Unused parameter h is not specified. For SchP00P meter, interface RS485 without galvanic isolation. |
|||||||
Ordering examples
SchP00P – 10kV/100V – × – × – × – R – 0.5, TU 25-7504.228-2015
For SchP00P meter, transformation factor of 10 kV/100 V with outer unit of balanced power supply of 5 V without interface, analogue and digital outputs; red indicators, accuracy class 0.5.
SchP01P – 100mA – 24V – 1RS – × – R – 0.5 – А, TU 25-7504.228-2015
For SchP01P meter, input signal measurement range 0...100 mA, supply voltage of 24 VDC (balanced), one interface RS485, without analogue and digital outputs, red indicators, accuracy class 0.5, custom design A, indication range 0...50 m.
SchP00P

SchP01P

SchP02.01P