Sch00P, Sch01P, Sch02.01P, Sch02.00
|
Type |
Overall dimensions, mm |
Sign height, mm |
Weight, kg, maximum |
|
Sch00P |
48 × 24 × 90 |
9.9 |
0.2 |
|
Sch01P |
96 × 24 × 90 |
9.9 |
0.2 |
|
Sch02.01P |
96 × 48 × 90 |
20 |
0.3 |
|
Sch02.00 |
96 × 48 × 64 |
9.9 |
0.2 |
|
Accuracy class |
– when measuring DC intensity and voltage – 0.1 or 0.2; – when converting – 0.5. |
|
Input signal |
mV: 60, 75, 100, 150, 200, 250, 500, 1000, 2000 V: 1, 2, 5, 10, 2…10, 20, 50, 100, 150, 200, 250, 300 (except for Sch00P), 500 (except for Sch00P); 750 (except for Sch00P, Sch01P) mA: 2, 5, 10, 20, 4…20, 50, 100, 200, 500, 1000, 2000 А: 1, 2 |
|
Temperature range (operating) |
-40 °С…+50 °С |
|
Maximum indication range |
Sch01P, Sch02.01P: 9999 ...+9999, Sch00P: 1999 ... + 9999, Sch02.00: 1999 ...+ 1999. |
|
Frequency range measured signals |
45...65 Hz |
|
Number of measuring channels |
1 |
|
Number of displayed parameters |
1 |
|
Galvanic isolation of input and output circuits, power circuits |
The meters have galvanic isolation in the power circuit, output circuits (Sch00P meters have no galvanic isolation in interface RS circuit). |
|
Front frame protection level |
IP50 |
|
Interface RS485 (protocol Modbus RTU) |
Quantity: 0 or 1 |
|
Interface exchange rate |
9600, 19200, 38400, 57600 bit/s. |
|
Analogue output (accuracy class 0.5) |
Quantity: 0, 1, 2 Ranges: 0...5 mA, 4...20 mA, 0…20 mA, 0...2.5...5 mA, 4...12...20 mA, 0…10…20 mA |
|
Load resistance, kΩ |
0.5 (for 4...20 mA, 0...20 mA, 4…12…20 mA, 0…10…20 mA) 2.5 (for 0...5 mA, 0…2.5…5 mA) |
|
Digital output |
Quantity: 0; 1; 2; DC voltage 300 V, 100 mA or AC voltage 200 V, 100 mA |
|
Maximum permissible input signal overload |
150% (2 hours) |
|
Time of setting output analogue signal, max |
0.5 s |
|
Input resistance at voltage measurement, min. |
(1±0.005) MΩ |
|
Power supply |
– 5 V (5±0.25) VDC, – 12 V (12±0.6) VDC, – 24 V (24±1.2) VDC, – 5 VN (5+4/-0.5) VDC, – 12 VN (12+6/-3) VDC, – 24 VN (24+12/-6) VDC; – outer unit of balanced supply voltage of 5 V (for Sch00P meter) |
|
Power consumption, max |
Sch00P – 1.7 VA; Sch01P – 2.7 VA; Sch02.01P – 3.2 VA; Sch02.00 – 2.5 VA |
|
Calibration interval |
10 years |
|
Guarantee period |
36 months |
|
Mean life, min |
20 years |
|
Mean time between failures |
200000 hours |
Order form
Scha – b – с – d – e – f – g – h
Scha – meter type (by the Overall dimension, mm):
Sch00P – 48×24,
Sch01P – 96×24,
Sch02.01P, Sch02.00 – 96×48,
b – reference designation of measurement range with direct connection or transformation factor with connection through the outside shunt
mV: 60, 75, 100, 150, 200, 250, 500, 1000, 2000
V: 1, 2, 5, 10, 2…10, 20, 50, 100, 150, 200, 250, 300
(except for Sch00P); 500 (except for Sch00P), 750 (except for Sch00P, Sch01P)
mA: 2, 5, 10, 20, 4…20, 50, 100, 200, 500, 1000, 2000
А: 1, 2
Note: if the indication range differs from the measurement range the input signal and from the shunt conversion factor, give additionally the ordered indication range in the note to the order formula.
c – reference designation of supply voltage:
5V, 12V, 24V, 5VN, 12VN, 24VN,
× – with outer unit of balanced supply voltage
5 V (for Sch00P meters);
d – availability of interface RS485:
1RS – one interface,
× – no interface;
e – reference designation of analogue and digital outputs:
01 – one digital outputs without analogue outputs,
10 – one analogue output without digital input,
11 – one analogue and one digital output,
12 – one analogue and two digital outputs,
20 – two analogue outputs without digital ones,
22 – two analogue and two digital outputs,
х – without analogue and digital outputs
Note: the reference designation of analogue output is specified after figures in brackets: А = 0...5 mA, В = 4...20 mA, С = 0...20 mA,
АР = 0...2.5...20 mA, ВР = 4…12…20 mA,
CР – 0…10…20 mA, when ordering two analogue outputs, specify it separated by a comma.
f – indicators colour:
R – red,
G – green,
Y – yellow;
g – accuracy class:
0.1 or 0.2;
Note – for Sch02.00 meter, accuracy class 0.2 only;
h – special design:
А – for operation at NPP (safety class 4),
– with the absence of custom design parameter is not specified.
|
Type |
Full reference designation code parameter |
||||||
|
b |
с |
d |
e |
f |
g |
h |
|
|
Sch00P |
+ |
×, 5В, 12В, 24В |
×, 1RS |
× |
+ |
+ |
+ |
|
Sch01P |
+ |
5В, 12В, 24В |
×, 1RS |
×, 01, 10, 11 |
+ |
+ |
+ |
|
Sch02.01P |
+ |
5ВН, 12ВН,24ВН |
1RS |
×, 12, 20, 22 |
+ |
+ |
+ |
|
Sch02.00 |
+ |
5В, 12В, 24В |
× |
× |
+ |
0,2 |
+ |
|
Notes Sign “+” means that availability of all possible versions of a parameter in the order formula. Sign “.” means that no parameter is available in the order formula. Unused parameter h is not specified. For Sch00P meter, interface RS485 without galvanic isolation. |
|||||||
Ordering examples
Sch00P – 10 mA – × – × – × – R – 0.1 TU 25-7504.228-2015
Sch00P meter, measurement range minus 10 to plus 10 mA, with outer unit of balanced supply voltage of 5 V without interface, analogue and digital outputs; red indicators, accuracy class 0.1.
Sch01P – 200А/75mV – 12V – 1RS – × – R – 0.1 TU 25-7504.228-2015
Sch01P meter, conversion factor of 200 A/75 mV, supply voltage of 12 VDC (balanced), one interface RS485, without analogue and digital outputs, red indicators, accuracy class 0.1.
Sch00P

Sch01P

Sch02.01P