Sch02P, Sch72P, Sch96P, Sch120P

Sch02P, Sch72P, Sch96P, Sch120P meters are intended to measure and convert current and voltage in DC circuits into output unified DC signals and serial digital interface RS485, which allow using the meters in automated systems of various purposes.
The meters provide the possibility for programming with built-in buttons or through the interface: indication range, decimal point position; level of the controlled values of input signals (settings); change in brightness of digital indicators illumination; interface parameters.
Sch120P meets the requirements of PJSC ROSSETI and PJSC FGC UES, they are recommended for the use at facilities of JSC ROSSETI and PJSC FGC UES.





Specifications
Documentation
Overall drawings
Related products

Type

Overall dimensions, mm

Panel cutout, mm

Sign height, mm

Weight, kg, max.

Sch02P

96 х 48 х 122

90 х 42

14

0.4

Sch72P

72 х 72 х 76

68 х 68

10

0.2

Sch96P

96 х 96 х 76

92 х 92

14

0.5

Sch120P

120 х 120 х 76

112 х 112

20

0.5

Accuracy class

0.1 or 0.2

Rated voltage

mV: 60, 75, 100, 150, 200, 250, 500, 1000, 2000

V: 1, 2, 5, 10, 2…10, 20, 50, 100, 150, 200, 250, 500, 750

Rated current

mA: 2, 5, 10, 20, 4…20, 50, 100, 200, 500, 1000

А: 1, 2

Temperature range (operating)

-40 °С... +70 °С UKhL3.1

Maximum indication range

-19999...+19999

Number of measuring channels

1

Galvanic isolation of input and output circuits, power circuits

Yes

Front frame protection level

IP50

Interface RS485 (protocol Modbus RTU)

– basic for data transmission

– additional for data transmission or connection of the display and indication modules (MI120, MI80)

Interface exchange rate

4600, 9600, 19200, 38400 bit/s.

Analogue output (accuracy class 0.5)

Quantity: 0; 1; 2;

Ranges: 0...5 mA, 4...20 mA, 0…20 mA, 0...2.5...5 mA;

4...12...20 mA; 0…10…20 mA

Load resistance

2.5 kΩ for ranges of 0...5 mA, 0...2.5...5 mA;

0.5 kΩ for ranges of 0...20 mA, 4...20 mA,

4...12...20 mA, 0…10…20 mA

Digital output

Quantity: 0; 1; 2;

DC voltage 300 V, 100 mA or

AC voltage 200 V, 100 mA

Maximum permissible input signal overload (from the upper limit of the measurement range)*

150% (1 minute)

Time of setting output analogue signal, max

1.0 s

Input resistance at load voltage measurement, min.

1 MΩ

Power supply parameters

– 5 VN (5+4/-0.5) VDC,

– 12 VN (12+6/-3) VDC,

– 24 VN (24+12/-6) VDC,

– 220 VU of 85...253 VAC, (50 ± 0.5) Hz or 120 ... 265 VDC

– 230 V from 85...253 VAC, (50 ± 0.5) Hz

Power consumption, max

6 V•А

Calibration interval

6 years

Guarantee period

36 months

Mean life

30 years

Mean time between failures

150000

Note: it is possible to connect the outer circuits according to the designation of connector contacts to the terminals “for screw” using a cord of up to 4 mm2 in cross-section, multi-core wires of up to 2.5 mm2. When connecting supply DC voltage of 120...265 V at supply voltage of 220 VU to power contacts “L”, “N”, any polarity is possible.

* Maximum input signal overload (from the rated value of the measurement range) 130% (2 hours).

Order form

Sch а – b – c – d – е – f – g – h

Sch – meter type (by the Overall dimension, mm):
Sch02P – 96×48,
Sch72P – 72×72,
Sch96P – 96×96,
Sch120P – 120×120,

b – measurement range for the input signal with direct connection or transformation factor with connection through the outside shunt
mV: 60, 75, 100, 150, 200, 250, 500, 1000, 2000
V: 1, 2, 5, 10, 2…10, 20, 50, 100, 150, 200, 250, 500, 750
mA: 2, 5, 10, 20, 4…20, 50, 100, 200, 500, 1000
А: 1, 2
Note: if the indication range differs from the measurement range the input signal and from the shunt conversion factor, give additionally the ordered indication range in the note to the order formula.

c – reference designation of supply voltage:
5 VN, 12 VN, 24 VN, 220 VU, 230 V

d – availability of interfaces RS485:
1RS – one interface,
2RS – two interfaces,
х – with the absence of parameter (for Sch120P only)

e – reference designation of analogue and digital outputs:
02 – two digital outputs without analogue output,
11 – one analogue and one digital output,
12 – one analogue and two digital outputs,
20 – two analogue outputs without digital ones,
22 – two analogue and two digital outputs,
х – without analogue and digital outputs
Note: the reference designation of analogue output is specified after figures in brackets: А = 0...5 mA, В = 4...20 mA, С = 0...20 mA,
АР = 0…2.5…5 mA, ВР = 4…12…20 mA, СР = 0…10…20 mA,
when ordering two analogue outputs, specify it separated by a comma.

f – indicators colour:
R – red, G – green, Y – yellow

g – accuracy class: 0.1 or 0.2

h – special design:
ОМ2 – meters for marine application,
А – for operation at NPP (safety class 4), do not specify in other cases.

Type

Full reference designation code parameter

b

с

d

e

f

g

h*

Sch02P

+

+

1RS

х, 12, 20, 22

+

+

+

Sch72P

+

+

1RS

х, 02, 11, 20

+

+

+

Sch96P

+

+

1RS, 2RS

х, 12, 20, 22

+

+

+

Sch120P

+

+

х,1RS, 2RS

х, 12, 20, 22

+

+

+

* For the meters with special design, accuracy class 0.2.

Notes

Sign “+” means that availability of all possible versions of a parameter in the order formula.

Sign “x” means that no parameter is available in the order formula.

Ordering example

Sch120P – 100 V – 220 V – 2 RS – 22(А,С) – R – 0.2 TU 25-7504.218-2012
Note: indication range -20…+50 °С
For Sch120P meter, measurement range minus 100 to plus 100 V, supply voltage of 85...253 VAC, 50 Hz or 120...265 VDC, two interfaces RS485, two analogue outputs 0…5 mA and 0…20 mA, two digital output, red indicators, accuracy class 0.2, indication range -20…+50 °С.

Сertificate of conformity (pdf, 2.5 Mb )   View   Download