Power Multi-Meter PQI120CP

UNDER DEVELOPMENT

The meter is geared to improvement of APCMS. PQI120CP is designed for revenue metering, measurement of power quality index (PQI), parameters of current, voltage, power, active and reactive power in 3ph mains and AC systems, as well as in points of meters mounting while keeping measurement results and displaying parameters of accounted electric power, PQI parameters and subsequent data transmission via communication interfaces.

PQI120CP is installed in the power quality monitoring and control systems for continuous monitoring of power quality indices of substations.

Full Compliance with Specified Russian Standards:

Power quality:
GOST 30804.4.30-2013
GOST 32144-2013
GOST R 51317.4.15-2012
GOST 30804.4.7-2013
GOST R 8.655-2009

Revenue metering:
GOST 31819.22-2012 (class 0.2S)
GOST 31819.23-2012 (class 1)

Mains parameters measurement:
GOST 22261-94
GOST R 52931-2008
GOST 29322-92

Power Quality Measurement and Monitoring
(Class А)
- rms voltage
- frequency
- duration and index of ACF and overvoltage
- duration of temporary overvoltage
- long- and short-term flicker indicator
- temporary overvoltage factor
- voltage n-harmonic component factor
- voltage waveform distortion factor
- negative-sequence voltage factor
- zero-sequence voltage factor

Multifunctional power meter  (Class 0.2S)
- metering of consumed active power based on cumulative total and separately according to rates
- eight rates
- active and reactive power
- active and reactive power loss
- energy recording malfunction flags

Mains parameters measurement and display
- current, class  0.2
- voltage, class 0.2
- electric power, class 0.5
- electric energy





Specifications

Dimensions, mm

180 х 280 х 85 mm

Operation Conditions

Temperature range

from -40 ОС to +60 ОС

Dust/moisture protection

IP51, GOST 14254

Resistance to mechanical effects

Group 4 as per GOST 22261

Electromagnetic compatibility

Interference immunity: GOST R 51317.6.5; Electromagnetic emission: ISCRI 22 for Class A

Power Supply

Power supply voltage

220 VU (universal) (from 90 to 264 VAC, (50 ± 0.5) Hz or from 130 to 370 VDC)

Power consumption

10 VA

Interfaces

Voltage inputs

Rated input voltages for 3/4-wire systems of - 100 V (limit voltage of
120 V) and 400 V (480 V)

Current inputs

Rated input phase currents is 1 A with measurement range of 2А, 5 А with measurement range of 10 A

Communication interface

Ethernet 10/100 BASE TX (connector RJ45) (2 pcs.) или
Ethernet 100 BASE FX (connector ST) (2 pcs.) ,
RS-485, fiber optic port - IEC 61107,
test pulse output

Local user interface

3 units of 7-segment indicators (4 indicators per each unit)

Communication Protocols

Remote human-machine interface

HTTP (embedded WEB-server)

Integration in telemetry systems

IEC 60870-5-104-2004 (Ethernet channel),
IEC 60870-5-101 (EIA RS-485 channel),
Optical interface “optical port” (IEC 61107),
Pulse output interface

Integration in the power quality monitoring system

HTTP (integration in PQI visualization and monitoring software package supplied in completion with the meter)

Integration in automated power supply monitoring and control system

 Enlargement of IEC 60870-5-101/104, IEC 61850-8-1

Meter time synchronization

NTP (RFC 5905)/PTP (IEEE `1588)

Functions of power quality indices
function of multi-rate meter

Back to list