Edgewise direct current and direct voltage meters М4247, М42248, М4248, М42200, М42201, М42243

This group of meters contains DC ammeters and voltmeters, which are used in switchboards, tile control panels and small equipment.
These meters could be manufactured for horizontal or vertical mounting with the relative location of the meter scale.
The protection level that is provided by cases of meters М4247, М4248 corresponds to IP53, meters 42248 – to IP20, other types of meters – to IP50. The protection level of live outputs is IP00.





Specifications
Documentation
Related products

Type

М4247

М42248

М4248

М42201

М42200

М42243

Overall dimension, mm

40х21

50х25

54х21

74х26

100х32

140х42

Panel cutout, mm

30.5х21

46.5х21.5

40.5х21

60.5х24.5

80.5х28.5

115х37

Scale length, mm, min.

20

27

27

40

60

94

Accuracy class

4.0

2.5

2.5; 4.0

1.5; 2.5

1.5*; 2.5

1.0

Weight, kg, maximum

0.035

0.08

0.04

0.20

0.25

0.5

* - except for μA

М42243

measurement range

connection method

operation conditions

mA– 5; 20

Directly

Temperature -50...+60 °С,

relative humidity 95 % at temperature +35 °С.

Vibration strength:

acceleration 2...15 m/s2,

frequency 10...70 Hz.

Shock resistance:

acceleration 50 m/s2,

frequency 10...50 impacts per min.

М42200, М42201

measurement range

connection method

operation conditions

μА – 100; 150; 200; 250; 300; 400;

500; 600; 750; 1000

Directly

Temperature -50...+60 °С,

relative humidity 95 % at temperature +35 °С.

Vibration strength:

acceleration 5...20 m/s2,

frequency 10...120 Hz.

Vibration strength:

acceleration 5...30 m/s2,

frequency 10...120 Hz.

Shock resistance:

acceleration 30 m/s2,

frequency 10...50 impacts per min.

Impact resistance:

acceleration 100 m/s2,

frequency 10...50 impacts per min.

mA– 1; 5; 10; 15; 30; 50; 100; 150;

300; 500; 600

А – 1; 2; 3; 5; 10

А – 20; 30; 50; 75; 100; 150; 200; 300; 500; 750; 1000; 1500; 2000; 3000; 4000; 6000

With outer shunt of 75 mV and calibrated wires of 0.035 Ω

А – 7500; 10000; 12500; 15000

With outer shunt of 100 mV and calibrated wires of 0.035 Ω

V – 2; 3; 7,5; 10; 15; 30; 50; 75; 100; 150; 250; 300; 450; 500; 600

Directly

V – 1000; 1500; 3000

With outer multiplying resistor at rated current 5 mA

М4247, М4248

measurement range

connection method

operation conditions

μА – 50*; 75*; 100; 150; 200; 250;

300; 400; 500; 600; 1000

Directly

Temperature -50...+60 °С, relative humidity 95 % at temperature +35 °С.

Impact resistance:

acceleration 100 m/s2,

frequency 10...50 impacts per min.

mA– 5**

* – with the zero position inside the measurement range only

** – for М4248 only

М42248 is the meter with increased endurance to mechanical effects intended for operation under conditions of NPP

measurement range

connection method

operation conditions

mA– 5; 20; 4-20

Directly

Temperature -10...+45 °С, relative humidity 98 % at temperature +35 °С.

Vibration strength: within the frequency range 5 to 30 Hz with acceleration of 40 m/s2; within the frequency range 30 to 150 Hz with acceleration of 9.8 m/s2.

Vibration strength: within the frequency range 5 to 100 Hz with acceleration of 80 m/s2.

Impact resistance: pulse duration 2...20 ms with acceleration of 200 m/s2.

6000 impacts.

mV – 75; 200

V – 1; 10; 2-10

 

Ordering examples

Milliammeter М42243, 0...10 kGs/см², 1.5, v, TU 25-7504.134-2008

For milliammeter М42243 manufactured for operation in conditions of moderate climate with the dust-proof scale design of 0...10 kGs/cm2, accuracy class 1.5; vertical operating position.

Milliammeter М42243 Т3, 0...10 kGs/см², 1.5, v, TU 25-7504.134-2008

For milliammeter М42243 manufactured meters for the operation in the tropical conditions with the dust-proof scale design of 0...10 kGs/cm2, accuracy class 1.5; vertical operating position.

Microammeter М42201(p), 100-0-100 µA, 1.5, v, TU 25-7504.134-2008

For microammeter М42201 manufactured for operation in conditions of moderate climate, having measurement range 100-0-100 µA, accuracy class 1.5, vertical operating position, dust-proof design.

Microammeter М4248, 0...100 µA, 2.5, v, Б, TU 25-7504.134-2008

For microammeter М4248 manufactured for operation in conditions of moderate climate, having measurement range 0...100 µA, accuracy class 2.5, vertical operating position, dust-proof design.

Microammeter М4247.1 TU 25-7504.134-2008

For microammeter М4247 with the special scale.

Microammeter М42248, 4...20 mA, 0...10 MPa, v – black, TU 25-7504.185-2005

For milliammeter М42248 with rated current of 4 to 20 mA, scale 0...10 MPa, the vertical operating position, black case.

For reference only:

v/g – vertical/horizontal operating position;

Т3 – meters for the operation in the tropical conditions.

М4247, М4248, М42200, М42201, М42243 Сertificate of conformity (pdf, 1.8 Mb )   View   Download
М42248 Сertificate of conformity (pdf, 6.7 Mb )   View   Download
М4247, М4248 Manual (pdf, 1.1 Mb )   View   Download
М42200, М42201, М42243 Manual (pdf, 317.4 Kb )   View   Download
Has been found to conform to requirements Russian Maritime Register of Shipping (pdf, 943.5 Kb )   View   Download
Back to list