SchV02.1, SchV72.1, SchV96.1, SchV120.1

SchV02.1, SchV72.1, SchV96.1, SchV120.1 meters are intended to measure and convert active, reactive and total power of one-phase AC circuits into output unified DC signals and serial digital interface RS485, which allow using the meters in automated systems of various purposes.
The meters provide the possibility for programming with built-in buttons or through the interface: indication range, decimal point position; level of the controlled values of input signals (settings); change in brightness of digital indicators illumination; interface parameters.





Specifications
Documentation
Overall drawings

Type

Overall dimensions, mm

Panel cutout, mm

Sign height, mm

Weight, kg, max.

SchV02.1

96 х 48 х148 (w/ protective cover)

96 х 48 х 121,5 (w/o cover)

92х45

20

0.4

SchV72.1

72 х 72 х 103 (w/ protective cover)

72 х72 х 75,6 (w/o cover)

68х68

14

0.4

SchV96.1

96 х 96 х 103 (w/ protective cover)

96 х 96 х 75,6 (w/o cover)

92х92

20

0.4

SchV120.1

120 х 120 х 103 (w/ protective cover) 120 х 120 х 75,6 (w/o cover)

112х112

20

0.5

Accuracy class

0.5

Temperature range (operating)

UKhL3.1 (-40... +50 °С)

Maximum indication range

-9999...+9999

Rated frequency range measured signals

50 Hz

Number of measuring channels

1 current input; 1 voltage input

Front frame protection level

IP50

Rated power factor

For wattmeter cosφ=1, for wattmeter sinφ=1

Interface RS485 (protocol Modbus RTU)

Interface RS485 (protocol Modbus RTU)

– basic for data transmission;

– additional for data transmission or connection of the display and Display panel (MI120, MI80)

(for SchV96.1, SchV12.1 only)

Interface exchange rate

4800, 9600, 19200, 38400 baud.

Analogue output (accuracy class 0.5)

Quantity: 0, 1, 2

Range: 0...5 mA, 0...2.5...5 mA, 0…20 mA, 4...12...20 mA, 4...20 mA, 0…10…20 mA

Digital output

Quantity: 0, 1, 2

DC voltage 300 V, 100 mA or

AC voltage 200 V, 100 mA

Maximum permissible input signal overload

150% (2 hours)

Measurement time, max.

0.1 s

Time of setting output analogue signal, max

0.5 s

Voltage drop when measuring current

30 mV

Power supply

– 5 VN (5+4/-0.5) VDC,

– 12 VN (12+6/-3) VDC,

– 24 VN (24+12/-6) VDC,

– 220 VU (85...253 VAC,

– (50 ± 0.5) Hz or 120 ... 265 VDC)

Power consumption, max

6 V•А

Guarantee period

2 years

Mean life

25 years

Mean time between failures

200,000

Note: outer connections are carried out with screw terminals ensuring connection of copper or aluminium wires of up to 2.5 mm2 in cross-section (diameter of 1.8 mm max.).

Order form

SchVa – b – c – d – e – f – g – h – i

а – meter type (by dimensions):

02.1 – 96×48; 72.1– 72×72; 96.1– 96×96; 120.1 – 120×120

b – rated voltage, or Kvt:

100 V, 380 V, 400 V – rated voltage;

U/100 – U rated voltage of the voltage transformer primary winding, secondary winding rated voltage of 100 V

c – rated current, or Kct:

0.5А, 1А, 2.5А, 5А – rated current;

I/1, I/5 – I rated current of the current transformer primary winding, secondary winding rated current of 1А or 5А

d – unit of measurement:

W, kW, MW, ±VAr, ±kVAr, ±MVAr, W/±VAr, kW/±kVAr, MW/±MVAr

e – power:

220 VU – universal power: supply voltage of 85 ...253 VAC, 50 Hz or 120...265 VDC;

5 VN – (5+4/-0.5) VDC;

12 VN – (12+6/-3) VDC;

24 VN – (24+12/-6) VDC

f – interface:

1 RS – one RS485 (main)

2 RS – two RS485 (main and additional) Note: meters SchV02.1, SchV72.1 are manufactured with one interface only (f = 1RS).

g – reference designations of measurement range output analogue signal

х – no parameter;

Х – one output analogue signal

(Example: А, В, С, ВР)

Х/Y – two output analogue signals

(Example: А/А; А/В; С/ВР) (А = 0…5 mA; В = 4…20 mA; С = 0…20 mA; АР = 0…2.5…5 mA; ВР = 4…12…20 mA; СР = 0…10…20 mA);

h – availability of analogue and digital outputs (designation depends on a number of output signals):

х – no parameter (with the absence of output analogue and digital signals);

20, 02, 11 – SchV72.1

12, 20, 22 – SchV96.1, 02.1, SchV120.1, where

11 – 1 analogue output, 1 digital output;

12 – 1 analogue output, 2 digital outputs;

02 – with no analogue output, 2 digital outputs;

20 – 2 analogue outputs with no digital output (the parameter is specified for a meter with the unit of displayed value х W/х VAr);

22 – 2 analogue outputs, 2 digital outputs (the parameter is specified for SchV120.1, SchV96.1, SchV02.1 design only with the unit of displayed value х W/х VAr);

I – Indication colour:

R – red; Y – yellow; G – green.

SchVa meter type

Full reference designation code parameter

Rated value or factor of transformation

Displayed parameter

Supply voltage

Number of interfaces

Number of analogue and digital outputs

Indication colour

b

с

d

e

f

g

h

SchV02.1

U

I

W, VAr, ±VAr

+

1RS

×, 12, 20, 22

+

SchV72.1

U

I

W, VAr, ±VAr

+

1RS

×, 02, 11, 20

+

W/VAR, W/±VAr

×, 02, 20

SchV96.1

U

I

W, VAr, ±VAr

+

1RS, 2RS

×, 12, 20, 22

+

W/VAR, W/±VAr

×, 20, 22

SchV120.1

U

I

W, VAr, ±VAr

+

1RS, 2RS

×, 12, 20, 22

+

W/VAR, W/±VAr

×, 20, 22

Notes

Sign “+” means that availability of all possible versions of a parameter in the order formula.

Sign “–” means that no parameter is available in the order formula.

Analogue output ranges are specified in brackets after a number of outputs.

Ordering example

SchV02.1 – 100V – 5А – MW – х – 220VU – 1RS – CP – 12 – З TU 25-7504.217-2015

For the meter with the following characteristics: type of SchV02.1 meter, rated voltage of 100 V, rated current of 5 A, power measurement unit is MW, no additional indication parameter, supply voltage of 85...253 VAC, 50 Hz or 120...265 VDC, one interface RS485, range change in output analogue signal of 0…10…20 mA, two digital outputs, green indication colour.

Сertificate of conformity (pdf, 1.3 Mb )   View   Download
Configurator (zip, 17.3 Mb )   View   Download

gabaryt_schv.jpg