Display panel MI120, MI80

Array
Specifications
Documentation
Overall drawings

Type

Overall dimensions, mm

Display weight

Displayed parameters

Climatic operation conditions

MI120.1

120 х 120 х 76

LED

P, Q, I

-40 °С... +70 °С, relative humidity of 95% max. at +35 °С

MI120.2

U

MI120.3

All parameters of meters and transducers: SchM20, SchM96, ENIP-2, Ye849EL, Ye900EL, Ye854EL, Ye856EL, Ye1854EL, Ye1856EL, Ye1858EL, SchK96, SchK120, Sch02P, Sch72P, Sch96P, Sch120P, SchP02P, SchP72P, SchP96P, SchP120P, SchV02.1, SchV72.1, SchV96.1, SchV120.1

MI120.5

colour liquid-crystalline display (touch-sensitive)

+1...+55 °С, relative ambient air humidity of 80% max. at +35 °С

MI80.3

80 x 80 х 85

LED

-40 °С... +70 °С, relative humidity of 95% max. at +35 °С

Interface

RS485 (protocol Modbus RTU)

For MI120.5 only:

Ethernet (for MI120.5 with RS485 design)

IEC 60870-5-104 (Ethernet channel),

IEC 60870-5-101 (EIA RS485 channel)

Additional options (for MI120.5 only)

The possibility for connection of outer SD-card (data archiving), availability of real time clock, events recording

Power supply

5 VN – (5+4/-0.5) VDC (except for MI120.5);

12 VN – (12+6/-3) VDC;

24 VN – (24+12/-6) VDC

220 VU – universal power: supply voltage of 85 to 253 VAC, 50 Hz or 120 to 265 VDC;

Power consumption, max

MI80.3 - 2 VA;

MI120.1, MI120.2, MI120.3 - 4 VA;

MI120.5 - 10 VA

Weight, kg, max.

0.4 kg (MI80.3 - 0.2 kg)

Guarantee period

24 months

Mean life

15 yeas (LCD – 10 years)

Mean time between failures

100,000 h

Order form

MI a b – с – d – e – f – g – h

MIa – module type:
MI80 – 80×80 (for multi-purpose LED only);
MI120 – 120×120.

b – design according to type of displayed parameters and indicator panels:
1 – load indication module (P, Q, I), LED – displays active and reactive power, average load current;
2 – voltage indication module (U), LED – displays phase or line voltages;
3 – multi-purpose indication module, LED – displays all basic measured and calculated parameters;
5 – multi-purpose indication module, colour touch-screen LCD
– displays all basic measured and calculated parameters.

c – reference designation of supply voltage:
5 VN – (5+4/-0.5) VDC (except for MI120.5);
12 VN – (12+6/-3) VDC;
24 VN – (24+12/-6) VDC;
220 VU – universal power: supply voltage of 85 to 253 VAC,
50 Hz or 120 to 265 VDC;

d – availability of digital interface RS485
х – with the parameter absence (for MI120.5 only, with RE design);
RS – availability of digital interface RS485;

e – availability of digital interface Ethernet (this parameter is used for MI120.5 only)
х – with the parameter absence (for MI120.5 only, with RS design);
RE – availability of digital interface Ethernet;

f – the possibility for connection of outer SD-card, the availability of real time clock (this parameter is used for MI120.5 only with the possibility of events recording)
х – with the parameter absence;
SD – the possibility for connection of outer USB-flash disk;

g – indicator colour or type:
G – green; R – red; Y – yellow;
TS – (“Touch Screen”) colour    liquid-crystalline display (this parameter is used for MI120.5 only);

h – custom design:
х – with the parameter absence


Ordering examples

MI120.1 – 220 VU – RS – x – x – G – х TU 25-7504.213-2011.
For the module with the following characteristics: 120×120 front frame size, basic load indication module, LED, supply voltage of 85 to 253 VAC, (50 ± 0.5) Hz or  120 to 265 VDC, the availability of digital interface RS485, indication colour – green.

MI120.1 – 24VN – RS – x – x – TS – х TU 25-7504.213-2011.
For the module with the following characteristics: 120×120 front frame size, multi-purpose load indication module, LCD, supply voltage of 24 VN DC, the availability of digital interface RS485.

MI120.5 – 12VN – x – RE – SD – TS – 10…9999Hz  TU 25-7504.213-2011.
For the module with the following characteristics: 120×120 front frame size, multi-purpose load indication module, colour touch sensitive LCD, supply voltage of 12 VN DC, the availability of digital interface Ethernet, the possibility of SD-card connection, the availability of real-time clock, input signal frequency.

MI120.5 – 12VN – RS – RE – SD – TS– х TU 25-7504.213-2011.
For the module with the following characteristics: 120×120 front frame size, multi-purpose load indication module, colour, touch sensitive LCD, supply voltage of 12 VN DC, the availability of digital interfaces RS485, Ethernet, the possibility of SD-card connection, the availability of real-time clock.

Manual (pdf, 2 Mb )   View   Download


gabaryt_en_mi.jpg
gabaryt_en_mi2.jpg

Back to list