SchUP96, SchUP120
|
Type |
Overall dimensions, mm, max |
Panel cutout, mm |
Sign height, mm, min |
Weight, kg, max. |
|
SchUP96 |
96х96х103 (w/ rear cover) |
92х92 |
20 |
0.4 |
|
SchUP120 |
120х120х103 (w/ rear cover) |
112х112 |
20 |
0.6 |
|
Maximum number of stages |
2...99 |
|
Stage resistance |
5...20 Ω (with pitch 1 Ω) |
|
Maximum measured resistance |
1000 Ω (999.9) |
|
Working Temperature range (operating) (climatic model O4.1) (climatic model UKhL3.1) |
+5 °С ...+50 °С -40 °С ... +55 °С |
|
Maximum current of relay output |
100 mA |
|
Maximum permissible voltage on relay output terminals |
300 V (by amplitude) |
|
Interface |
RS485 (protocol Modbus RTU) |
|
Front frame protection level |
IP2Х |
|
Power supply voltage |
85...242 VAC, (50±0.5) Hz or 120 ...265 VDC |
|
Power consumption |
7 V•A |
|
Mean time between failures, min |
10000 h |
|
Mean life, min |
10 years |
Order form
а – meter type (by dimensions):
96; 120
b – stage resistance value*:
5...20
* – with the absence in the order, by default 6 Ω is accepted
c – interface:
RS – interface RS485 (Modbus RTU);
х – in case of interface absence,, it is not specified
d – indicators colour:
R – red
G – green
Y – yellow
e – climatic model:
О4.1 – +5 °C ...+50 °C;
UKhLЗ.1 – -40 °C ... +55 °C
Ordering example
SchUP120 – 6 – RS – R – UKhL 3.1 TU 25-7504.205-2008
The SchUP120 indicator, stage resistance of 6 Ω, interface RS485, red indicators, working Temperature range (operating) -40 °С ...+55 °С.