E900EL

E series converters are intended to measure and convert electrical parameters in 3-phase 3-wire and 3-phase 4-wire electrical AC mains into the unified output DC signals and sequence of digital signals for transmission through interfaces RS485, Ethernet (protocols Modbus RTU, Modbus TCP, IEC 60870-5-101, IEC 60870-5-104).

E series converters may be used for:

– control of main electrical parameters in 3-phase mains;

– technical metering of electric power.





Specifications
Documentation
Overall drawings
Related products

Type

Overall dimensions, mm, max

Weight, kg, max.

E900EL

162х90х61мм

0.7


Parameters of 3-phase mains

Designation

Measured parameters

Effective phase voltage value

UA, UB, UC

+

Average effective phase voltage value

U

+

Effective line-to-line voltage value

UAB, UBC, UCA

+

Average effective line-to-line voltage value

Ul

+

Effective phase current value

IA, IB,IC

+

Average effective phase current value

I

+

Active load phase power

PA, PB, PC

+

Total active power

P

+

Reactive load phase power

QA, QB, QC

+

Total reactive power

Q

+

Full load phase power

SA, SB, SC

+

Total gross reactive power

S

+

Phase power factor

cosφA, cosφB, cosφC

+

Total power factor

cosφ

+

Frequency

F

+

Active power

WP

+

Reactive power

WQ

+

Power quality parameters

Frequency deviation, Hz (-5...5 Hz)

+

Voltage drop duration, s (0.02...60 s)

+

Voltage drop depth, % (10...99 %)

+

Voltage interruption duration, s (0.02...60 s)

+

Temporary overvoltage duration, s (0.02...60 s)

+


Information display

LED indication (single indicators)

– supply voltage;

– digital inputs condition;

– phase sequence indicator;

– Interface RS485 operation;

– relay output condition;

– event indicator

LCD (by order)

Coloured; LCD dimension: 46.7х35.4 mm (2.2”)

Additional features

Connection of Display panel MI120, MI80 via interface RS485, Ethernet

Telemetry

Input signal

Current, A:

Voltage, V:

Frequency, Hz:

1.0; 5.0; range 0...2.0 Irated

100, 380, 400; range 0...1.2 Urated

45...55

Measurement time

0.1 s

Time of setting output analogue signal, max

0.5 s

Basic error limits

by current and voltage: ± 0.2%; by power: ± 0.5 %; by frequency: ± 0.01 Hz;

by analogue output: ± 0.5%

Galvanic isolation of input and output circuits, power circuits

Yes

Short-term overloads by input signal with briefness (maximum)

Briefness: 20; number of overloads: 2; duration of each overload, s: 0.5; interval between two overloads, s: 0.5.

Input resistance:

by current circuits, max.

by voltage circuits, min.


0.02 Ω

1 MΩ

Communication interfaces/Analogue outputs

RS485

Quantity: 1, 2; protocols: Modbus RTU, IEC 60870-5-101

Data rate: 4800, 9600, 19200, 38400, 57600 baud.

Ethernet

Quantity: 0, 1, 2; 100 BASE TX; protocols: Modbus TCP, IEC 60870-5-104

Analogue output

Quantity: 0, 1, 2, 3; reprogrammed ranges: 0…5 mA, 4…20 mA, 0…20 mA, 0…2.5…5 mA, 4…12…20 mA, -5…0…+5 mA, 0...10...20 mA

Telesignaling

Digital inputs

Quantity: 8; “dry contact” type, voltage =24 V, current 10 mA

Telecontrol

Relay outputs

Quantity: 0, 1, 2, 3 (switch on/off, locking); voltage ~250 V, =30 V, current 5 A

Supply voltage

Power supply

– 24 VN (24+12/-6) VDC

– 220 VU (90...264 VAC (50 ±0.5) Hz or 130...370 VDC)

– measuring circuit

Power consumption from power circuit, max.

7 VA

Device reprogramming (tuning)

Reprogramming

– via program “Konfigurator” (interface RS485, Ethernet);

– via Web-interface (interface Ethernet);

– with buttons on the front panel (if available)

Reprogramming parameters

– connection diagram (3- or 4-wire);

– indication range (devices with rated currents of 1 A, 5 A and voltage of 100 V);

– password setting;

– indication update period: from 0.1 to 10 s;

– decimal point position;

- settings for each electrical value (if digital outputs available - up to 3 control signals for switching equipment);

– interfaces RS485, Ethernet;

– output signals parameters;

- indication brightness;

– parameters of protocol Modbus RTU, Modbus TCP, IEC 60870-5-101, IEC 60870-5-104 (via program “Konfigurator“, Web-interface);

– calibration of input and output signals.

Operation Conditions

Temperature range (operating)

from -40°С to +70°С

Protection level

IP20 according to GOST 14254-96

Installation

DIN-rail 35 mm

Wires section

2.5 mm2

Maximum input signal overload (duration)

150 % (2 hours)

Calibration interval

11 years (8 years - LCD display)

Guarantee period

24 months

Mean life, min

20 years

Mean time between failures

250000 hours


Order form

E a – b – c – d – e – f – g – h – i – j – k

а – converter type depending on functional possibilities:

900EL – multifunctional converter;

b – rated voltage:

100 V, 380 V, 400 V – line voltage;

U/100 – voltage transformation ratio (rated secondary winding voltage 100 V);

c – rated current:

1.0 А; 5.0 А – phase current;

I/1; I/5 – current transformation ratio (rated secondary winding current 1 А and 5 А);

d – reference designation of supply voltage:

24 VN – DC supply voltage of (24+12/-6) V;

220 VU – universal power: supply voltage 90 to 264 VAC 50 Hz or 130 to 370 VDC;

from the measuring circuit within range 85 ...253 V;

e – reference designation for availability of interfaces RS485:

1RS – availability of main interface RS485;

2RS – availability of main and additional interfaces RS485;

f – reference designation for availability of interfaces Ethernet:

х – specified when not needed;

1RE – availability of one interface Ethernet;

2RE – availability of two interfaces Ethernet;

g – reference designation of 8 digital inputs:

х – specified when not needed;

DI – availability of 8 digital inputs;

h – reference designation of output signals:

х – specified when not needed;

01 – one digital output without analogue outputs,

02 – two digital outputs without analogue outputs;

03 – three digital outputs without analogue outputs;

10(а) – one analogue output without digital outputs;

11(a) – one analogue and one digital output;

12(a) – one analogue and two digital outputs;

13(a) – one analogue and three digital outputs;

20(а,b) – two analogue outputs without digital ones;

21(а,b) – two analogue and one digital output;

22(а,b) – two analogue and two digital outputs;

23(а,b) – two analogue and three digital outputs;

30(а,b,c) – three analogue outputs without digital ones;

31(а,b,c) – three analogue and one digital output;

32(а,b,c) – three analogue and two digital outputs;

33(а,b,c) – three analogue and three digital outputs;

where а,b,c – reference designations of measurement ranges of output analogue signals

(А = 0...5 mA; В = 4...20 mA; С = 0...20 mA; АР = 0…2.5…5 mA; ВР = 4…12…20 mA; СР = 0…10…20 mA; ЕР = -5…0…5 mA)

(Example: (12(А); 21(В,В); 33(С,А,В); 30(С,В,С));

i – indication type:

х – specified when not needed;

LCD – colour, liquid-crystalline, touch sensitive.

j – operational design:

х – for general industrial use;

ОМ2 – for operation in marine vessels;

А – for operation at NPP (safety class 4);

Ordering examples

E900EL – 400V – 5А – 220VU – 1RS – 2RE – DI – 33(А,В,А) – х – х TC 25-7504.232-2016

For multifunctional converter with the following characteristics: rated voltage of 400 V, rated current of 5 A, supply voltage 90 to 264 VAC 50 Hz or 130 to 370 VDC, main interface RS485, two interfaces Ethernet, digital inputs, three analogue outputs 0…5 mA, 4…20 mA, 0...5 mA, three digital outputs.

Сertificate of conformity (-ob-utv, 683.4 Kb )   View   Download