E1856EL

Direct current and direct voltage measuring converters E1856EL are intended for current and voltage measurement in one-phase DC circuits.
The converters may be used to control current and voltage of electrical systems and installations, as well as for automation of different electric power industry facilities, fields of defense, safety and industry.





Specifications
Documentation
Overall drawings
Related products

Type

Overall dimensions, mm, max

Weight, kg, max.

E1856EL

24 х 111 х 116

0.3

Input signal

0...5 mA, 4...20 mA, 0…20 mA, -5...0...5 mA

0...75 mV; -75...0...75 mV; 0...60 V; 0...100 V; 0...150 V; 0...250 V; 0...500 V

Basic error limits

±0,5%

Temperature range (operating)

-40 °С... +50 °С

Protection extent

IP50

Interface

RS485 (Мodbus RTU) – main, for data transmission

Data rate

4800, 9600, 19200, 38400 bit/s.

Parameters setting (reprogramming) through the interface

– digital output;

– interface RS485 (Modbus RTU) parameters;

– analogue output signal parameters

Analogue output

Quantity: 0, 1

Ranges: 0...5 mA; 0...20 mA; 4…20 mA; 0...2.5...5 mA; 4…12…20 mA; 0…10…20 mA; -5…0…5 mA

Digital output

DC voltage: 300 V; 100 mA

AC voltage: 200 V; 100 mA

Maximum input signal overload

150%, duration of 2 hours

Time of setting output analogue signal, max

0.5 s

Installation

DIN-rail of 35 mm

Power supply

220 VU – universal power: supply voltage of 85 to 253 VAC,

50 Hz or 120 to 265 VDC;

230 V – supply voltage of 85...253 VAC 50 Hz;

12 VN – (12+6/-3) VDC;

24 VN – (24+12/-6) VDC

Power consumption from power circuit, max.

6.0 V•А

Power consumption

by voltage circuits, max:

by current circuits, max:

0.5 W

0.01 W

Calibration interval

8 years

Guarantee period

2 years

Mean life

20 years

Mean time between failures

200000 hours

Order form

E1856EL – а –b – с – d – f

a – input signal measurement ranges:

0...5 mA, 4...20 mA, 0...20 mA, -5...0...5 mA,

0...75 mV, -75...0...75 mV, 0...60 V, 0...100 V,

0...150 V, 0...250 V, 0...500 V

b – supply voltage:

220 VU – universal power: supply voltage of 85 to 253 VAC, 50 Hz or 120 to 265 VDC;

230 V – supply voltage of 85...253 VAC, 50 Hz;

12 VN – (12+6/-3) VDC;

24 VN – (24+12/-6) VDC

c – measurement range analogue output signal:

А = 0...5 mA; В = 4...20 mA;

С = 0...20 mA; АР = 0…2.5…5 mA; ВР = 4…12…20 mA;

СР = 0…10…20 mA; ЕР = -5…0…+5 mA; x – with the absence

d – digital output availability:

х – no output

01 – one digital output

f – custom design:

А – operation at NPP

(safety class – 4).

With the absence of custom design parameter is not specified.

Ordering example

E1856EL – 0…20mA – 220VU – СР – 01 TU 25-7504.226-2014

For the transducer with the following characteristics: transducer type E1856EL, measurement range input signal of 0...20 mA, supply voltage of 85...253 VAC, 50 Hz or 120...265 VDC, measurement range analogue output signal of 0…10…20 mA, digital output.

Сertificate of conformity (jpg, 451.2 Kb )   View   Download
Manual (pdf, 1.2 Mb )   View   Download
Configurator (zip, 17.3 Mb )   View   Download


gabaryt_e1858el.jpg

Back to list